# Enclosure Mounting

Enclosures must be solidly installed in dry well vented environment; may be flush mounted or surface mounted.
Surface mounted enclosures should be installed on a ¾’’ plywood reinforced wall. Flush mounted enclosures need to be affixed between stud bays. For best results, 5/8in. (16mm) drywall is preferred.

  • Refer to maximum weight capacity.

  • Consult our website for driver measurements and weight.

  • Enclosures are intended for indoor use only. Dry location only.

  • Enclosures house equipment that requires being air-cooled, mount in a well-ventilated area.

  • The ambient temperature range is 32°F to 104°F (0°C to 40°).

  • The relative humidity range is 10% to 90% (non-condensing).

  • Allow adequate clearance in front of the vented cover for servicing and ventilation.

surface and flush mounted

# Electrical Distribution

Warning

ALL POWER FEEDS MUST BE PROTECTED BY A DEDICATED 20 AMP CIRCUIT BREAKERS, SUPPLIED AND INSTALLED BY CERTIFIED ELECTRICIANS IN ACCORDANCE TO LOCAL AND NATIONAL ELECTRICAL CODES.

  • Enclosure must be wired by a certified low voltage installer in accordance with all local codes.

  • Enclosure should be grounded as per local and national electrical codes.

  • Never load electrical breakers at more then 80% capacity.

  • Calculate AC amperage consumption to determine appropriate electrical requirements and electrical distribution in each enclosures.

  • Use 12/2 cable for external electrical distribution.

  • Use copper conductors only – rated at 60°C.

  • Low voltage and AC should be run within the enclosure separately.

  • If more then one circuit is necessary in a same enclosure, use same electrical phase.

Electrical lateral connection 15A outlet parts

# Equipment power consumption

Power Supply Usage @ 80%

WATTS DC AMP AC AMP
HLG-320-24 13.4A 240 10 1.81
HLG-240-24 10A 192 8 1.45
HLG-100-24 4A 96 3.2 0.6
CBNA-200-Z4 NA 1050 mA 1.55
PS-SR2112-96 96 2

Wire Placement

# Component Configuration

  • Refer to our website for specifications regarding maximum weight capacity.

  • Keep AC separated from low voltage using our included bracket lacing.

  • Use provided nylon grommets to protect any wires from damage at top and bottom of enclosure.

  • Leave space between drivers for aeration purpose.

Enclosure with components

Colorbeam Lighting offers in-factory system configuration and / or assembly should alternate UL certified configurations be required.

Contact Colorbeam Lighting for applicable fees.